Toronto District School Board
Toronto District School Board
Icon - Find Your School  Find Your School|New to Canada|Policies|Media
About Us|Staff|Employment|Leadership|Contact Us
Translate
Close Window X

Google Translate Limitations Disclaimer

The electronic translation service on the Toronto District School Board website is hosted by Google Translate, a third party service. The TDSB does not guarantee or warrant the reliability, accuracy or completeness of any translated information.

The quality of the translation will vary in some of the languages offered by Google. Google Translate is a free service and currently offers translation in over 100 languages, but does not capture all languages or dialects.

The basic translation goal is to capture the general intention of the original English material. Before you act on translated information, we encourage you to confirm any facts that are important to you or may affect any decisions you make.

The Toronto District School Board is committed to equity and community engagement, and by providing this tool, we are making our information more accessible to families whose first language is not English.

Google Translate Frequently Asked Questions

Central Technical School (GR. 09-12)

Health and Safety (H&S) workplace inspections are conducted every month in all of our 582 operating schools. Below you can find the H&S reports for your school, for the 2017-2018 school year.  More information and Frequently Asked Questions

Date InspectedLocation in SchoolHealth & Safety Issue ObservedClassAction Taken ByDate Action TakenDetails
09/19/17113hazard (provide details)BCentral Technical School10/12/17Details
09/19/17b114hazard (provide details)BCentral Technical School10/12/17Details
09/19/17B 102 hazard (provide details)BCentral Technical School10/12/17Details
09/19/17Bathurst Building 2nd fl mech roomunable to inspect (specify why if possible)BCentral Technical School10/12/17Details
09/19/17139 autohazard (provide details)BCentral Technical School10/12/17Details
09/19/17141 autoeyewash station required or in need of repair (specify)ACentral Technical School10/12/17Details
09/19/17441 and 442eyewash station required or in need of repair (specify)ACentral Technical School10/12/17Details
09/19/17154egress blocked or insufficient path (doorway, hallway or stairwell)BCentral Technical School10/12/17Details
09/19/17B108eyewash station required or in need of repair (specify)ACentral Technical School10/12/17Details
10/02/17127guarding or shielding not in placeACentral Technical School11/01/17Details
10/02/17Fan Room 240guarding or shielding not in placeACentral Technical School11/01/17Details
10/02/17Fan Room in caretaker office areaguarding or shielding not in placeACentral Technical School11/01/17Details
10/02/17432fire exit route sign (yellow TDSB) - not posted / requires updatingBCentral Technical School01/04/18Details
10/02/17445fire exit route sign (yellow TDSB) - not posted / requires updatingBCentral Technical School01/04/18Details
10/02/17137equipment damaged or not securedBCentral Technical School11/01/17Details
10/02/17453equipment damaged or not securedBCentral Technical School01/04/18Details
10/02/17433A toxic waste storageunable to inspect (specify why if possible)BCentral Technical School01/04/18Details
10/02/17141trip hazard (i.e. flooring, wiring, other materials)ACentral Technical School01/04/18Details
10/02/17439door not opening or closing properly (interior or exterior)ACentral Technical School01/04/18Details
10/02/17433eyewash station required or in need of repair (specify)ACentral Technical School01/04/18Details
10/02/17118eyewash station required or in need of repair (specify)ACentral Technical School11/01/17Details
10/02/17All Buildingsemployee voice concernsBCentral Technical School11/01/17Details
10/02/17139receptacle/light switch (specify)ACentral Technical School11/01/17Details
10/02/17453lighting in need of repairACentral Technical School01/04/18Details
10/02/17441window damaged, in need of repair (specify)ACentral Technical School01/04/18Details
10/02/17443ceiling damaged (specify)ACentral Technical School01/04/18Details
10/02/17A111 Fan Roomportable ladder - damaged or not securely storedACentral Technical School11/01/17Details
11/16/17Dark Room in 105eyewash station required or in need of repair (specify)ACentral Technical School01/04/18Details
11/16/17B114portable ladder - damaged or not securely storedACentral Technical School01/04/18Details
11/16/17151damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School01/05/18Details
11/16/17107, 420, 417 & 414ceiling damaged (specify)ACentral Technical School01/05/18Details
11/16/17107exposed wiring/damaged cord/ground pin missingACentral Technical School01/05/18Details
11/16/17Exit 24 B Buildingemployee voice concernsBCentral Technical School01/05/18Details
11/16/17Boiler Room - Main - Basementunable to inspect (specify why if possible)BCentral Technical School01/04/18Details
11/16/17B211 and B300unable to inspect (specify why if possible)BCentral Technical School01/04/18Details
11/16/17410egress blocked or insufficient path (doorway, hallway or stairwell)BCentral Technical School01/05/18Details
11/16/17139, 150, 426, 420, & 417fire exit route sign (yellow TDSB) - not posted / requires updatingBCentral Technical School01/05/18Details
11/16/17403 and 417extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCentral Technical School01/05/18Details
11/16/17240guarding or shielding not in placeACentral Technical School01/05/18Details
11/16/17Fan Room - Main - Basementleaking/pooling/ponding of water or liquid (be as specific as possible)ACentral Technical School01/05/18Details
12/06/17Fan Room above stageguarding or shielding not in placeACentral Technical School01/04/18Details
12/06/17B300unable to inspect (specify why if possible)BCentral Technical School01/04/18Details
12/06/17B111unable to inspect (specify why if possible)BCentral Technical School01/04/18Details
12/06/17150equipment damaged or not securedBCentral Technical School01/04/18Details
12/06/17139equipment damaged or not securedBCentral Technical School01/04/18Details
12/06/17137equipment damaged or not securedBCentral Technical School01/04/18Details
12/06/17Boiler Room - Main - BasementACM - yellow asbestos bags present (incl. number of bags)A1Central Technical School01/04/18Details
12/20/17139inspections not up to date (specify equipment)BCentral Technical School04/03/18Details
12/20/17137inspections not up to date (specify equipment)BCentral Technical School04/03/18Details
12/20/17150inspections not up to date (specify equipment)BCentral Technical School04/03/18Details
12/20/17B9 Pool Filter Roominsufficient means of communication (ie: PA, radio, etc.)BCentral Technical School04/03/18Details
12/20/17106insufficient means of communication (ie: PA, radio, etc.)BCentral Technical School04/03/18Details
12/20/17B108extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCentral Technical School04/03/18Details
12/20/17150leaking/pooling/ponding of water or liquid (be as specific as possible)ACentral Technical School04/03/18Details
12/20/17147leaking/pooling/ponding of water or liquid (be as specific as possible)ACentral Technical School04/03/18Details
12/20/17Fan Room - Main - Basementleaking/pooling/ponding of water or liquid (be as specific as possible)ACentral Technical School04/03/18Details
12/20/17Boiler Room - Main - Basementleaking/pooling/ponding of water or liquid (be as specific as possible)ACentral Technical School04/03/18Details
12/20/17141inspections not up to date (specify equipment)BCentral Technical School04/03/18Details
12/20/17107exposed wiring/damaged cord/ground pin missingACentral Technical School04/03/18Details
12/20/17127eyewash station required or in need of repair (specify)ACentral Technical School04/03/18Details
12/20/17114damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School04/03/18Details
12/20/17148leaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/03/18Details
12/20/17B101exposed wiring/damaged cord/ground pin missingACentral Technical School04/03/18Details
02/05/18150leaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/03/18Details
02/05/18150leaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/03/18Details
02/05/18139damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School04/03/18Details
02/05/18A204damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School04/03/18Details
02/05/18107receptacle/light switch (specify)ACentral Technical School04/03/18Details
02/05/18422eyewash station required or in need of repair (specify)ACentral Technical School04/03/18Details
02/05/18Boiler Room - Main - Basementleaking/pooling/ponding of water or liquid (be as specific as possible)ACentral Technical School04/03/18Details
02/05/18A204guarding or shielding not in placeACentral Technical School04/03/18Details
02/05/18kitchenextinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/03/18Details
02/05/18B9 Pool Filter Roominsufficient means of communication (ie: PA, radio, etc.)BCentral Technical School04/03/18Details
03/25/18Caretakers' Lunch Roomceiling damaged (specify)ACentral Technical School04/27/18Details
03/25/18Electrical Room under stair #6inappropriate storage of materials/furniture/shelving, or clutterBCentral Technical School04/27/18Details
03/25/18B Pool Tunnelleaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/27/18Details
03/25/18B Pipe Tunnelleaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/27/18Details
03/25/18B210 Galleryleaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/27/18Details
03/25/18B210 Galleryleaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/27/18Details
03/25/18Boiler Room - Main - Basementleaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/27/18Details
03/25/18Fan Room in caretaker office arealeaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/27/18Details
03/25/18154 Officedamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School04/27/18Details
03/25/18154 Officedamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School04/27/18Details
03/25/18A111 Fan Roomportable ladder - damaged or not securely storedACentral Technical School04/27/18Details
03/25/18Boiler Room - Main - Basementportable ladder - damaged or not securely storedACentral Technical School04/27/18Details
03/25/18B8 Mechanical Roomfire extinguisher not adequately charged or mountedACentral Technical School04/27/18Details
03/25/18Boiler Room - Main - Basementfire extinguisher not adequately charged or mountedACentral Technical School04/27/18Details
03/25/18B9 Pool Filter Roomeyewash station required or in need of repair (specify)ACentral Technical School04/27/18Details
03/25/18118eyewash station required or in need of repair (specify)ACentral Technical School04/27/18Details
03/25/18439door not opening or closing properly (interior or exterior)ACentral Technical School04/27/18Details
03/25/18B124trip hazard (i.e. flooring, wiring, other materials)ACentral Technical School04/27/18Details
03/25/18141trip hazard (i.e. flooring, wiring, other materials)ACentral Technical School04/27/18Details
03/25/18127trip hazard (i.e. flooring, wiring, other materials)ACentral Technical School04/27/18Details
03/25/18Boiler Room - Main - Basementguarding or shielding not in placeACentral Technical School04/27/18Details
03/25/18121guarding or shielding not in placeACentral Technical School04/27/18Details
03/25/18Fan rm outside 609guarding or shielding not in placeACentral Technical School04/27/18Details
03/25/18B12 Electrical Roomextinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/27/18Details
03/25/18B211 Mechanical Roomextinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/27/18Details
03/25/18Caretaker - Storageextinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/27/18Details
03/25/18Boiler Room - Main - Basementextinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/27/18Details
03/25/18117 kiln roomextinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/27/18Details
03/25/18443extinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/27/18Details
03/25/18Fan Room above stageextinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/27/18Details
03/25/18Fan Room 240extinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/27/18Details
03/25/18fan room across from 235extinguisher - tag missing or annual inspection more than 3 months overdueACentral Technical School04/27/18Details
03/25/18Fan Room - Main - BasementACM - yellow asbestos bags present (incl. number of bags)A1Central Technical School04/27/18Details
03/25/18B125unable to inspect (specify why if possible)BCentral Technical School04/27/18Details
03/25/18B Pipe Tunnelinappropriate storage of materials/furniture/shelving, or clutterBCentral Technical School04/27/18Details
03/25/18B123 Receiving inappropriate storage of materials/furniture/shelving, or clutterBCentral Technical School04/27/18Details
03/25/18Boiler Room - Main - Basementinappropriate storage of materials/furniture/shelving, or clutterBCentral Technical School04/27/18Details
03/25/18443ceiling damaged (specify)ACentral Technical School04/27/18Details
04/26/18152ceiling damaged (specify)ACentral Technical School04/27/18Details
04/26/18Office - MainHealth & Safety bulletin board - required items are missing or outdated (be specific)BCentral Technical School04/27/18Details
04/26/18Boiler Room - Main - Basementleaking/pooling/ponding of liquid (specify liquid and source if possible)ACentral Technical School04/27/18Details
04/26/18B101damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School04/27/18Details
04/26/18152damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School04/27/18Details
04/26/18154damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School04/27/18Details
04/26/18221, 236 & 251damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School04/27/18Details
04/26/18Exit 2 railinghandrail not secure, damaged or requiredACentral Technical School04/27/18Details
04/26/18107receptacle/light switch (specify)ACentral Technical School04/27/18Details
04/26/18Hall by B102emergency lighting damaged/missing ACentral Technical School04/27/18Details
04/26/18B9ventilation (specify)ACentral Technical School04/27/18Details
04/26/18B114portable ladder - damaged or not securely storedACentral Technical School04/27/18Details
04/26/18Seminar Room 1door not opening or closing properly (interior or exterior)ACentral Technical School04/27/18Details
04/26/18Auditorium Fan Roomleaking/pooling of water on equipment (be as specific as possible)ACentral Technical School04/27/18Details
04/26/18Fan Room 240guarding or shielding not in placeACentral Technical School04/27/18Details
04/26/18205insulation - required or in need of repairACentral Technical School04/27/18Details
04/26/18247 & 255extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCentral Technical School04/27/18Details
04/26/18269 - Gymfire exit route sign (yellow TDSB) - not posted / requires updatingBCentral Technical School04/27/18Details
04/26/18139, 141 & 150inspections not up to date (specify equipment)BCentral Technical School04/27/18Details
04/26/18132 Storageemployee voice concernsBCentral Technical School04/27/18Details
04/26/18443fume hood - inspection is not up to dateBCentral Technical School04/27/18Details
04/26/18262, Lib. off, 443 & 252ceiling damaged (specify)ACentral Technical School04/27/18Details
05/22/18A302guarding or shielding not in placeACentral Technical School05/31/18Details
05/22/18Boiler Room - Main - BasementACM - yellow asbestos bags present (incl. number of bags)A1Central Technical School05/31/18Details
05/22/18A306insufficient means of communication (ie: PA, radio, etc.)BCentral Technical School05/31/18Details
05/22/18A304insufficient means of communication (ie: PA, radio, etc.)BCentral Technical School05/31/18Details
05/22/18Caretaker - ReceivingACM - yellow asbestos bags present (incl. number of bags)A1Central Technical School05/31/18Details
06/19/18347damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACentral Technical School07/31/18Details
06/19/18441eyewash station required or in need of repair (specify)ACentral Technical School07/31/18Details
06/19/18121exposed wiring/damaged cord/ground pin missingACentral Technical School07/31/18Details
06/19/18346exposed wiring/damaged cord/ground pin missingACentral Technical School07/31/18Details
06/19/18352extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCentral Technical School07/31/18Details
06/19/18Boiler Room - Main - Basementleaking/pooling/ponding of water or liquid (be as specific as possible)ACentral Technical School07/31/18Details
06/19/18Boiler Room - Main - BasementACM - yellow asbestos bags present (incl. number of bags)A1Central Technical School07/31/18Details
06/19/18113extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCentral Technical School07/31/18Details
06/19/18B101exposed wiring/damaged cord/ground pin missingACentral Technical School07/31/18Details