| Date Inspected | Location in School | Health & Safety Issue Observed | Class | Action Taken By | Date Action Taken | Details |
| | 175 - Auto Shop | inspections not up to date (specify equipment) | B | Caretaker | | Details |
| | Mech Rm D (in weight room) | inappropriate storage of materials/furniture/shelving, or clutter | B | Caretaker | | Details |
| | General Concern | combustible material being displayed that is not fire rated/treated | B | Caretaker | | Details |
| | 117 | insufficient means of communication (ie: PA, radio, etc.) | B | | | Details |
| | 175 - Auto Shop | insufficient means of communication (ie: PA, radio, etc.) | B | | | Details |
| | 173 - Cafeteria | insufficient means of communication (ie: PA, radio, etc.) | B | | | Details |
| | 126 | multiport in use - potential fire hazard | B | Caretaker | | Details |
| | 125 | multiport in use - potential fire hazard | B | Caretaker | | Details |
| | 113 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | | Details |
| | 115 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | | Details |
| | 114 - Chemical Prep Room | fume hood - improper use (not to be used for storage) | B | Caretaker | | Details |
| | 115 | insufficient means of communication (ie: PA, radio, etc.) | B | | | Details |
| | 125 | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | M8 - beside W22 | insufficient means of communication (ie: PA, radio, etc.) | B | | | Details |
| | Office - Principal | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Office - Principal | ceiling tiles missing/loose | A | Caretaker | | Details |
| | 114 - Chemical Prep Room | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | 114 - Chemical Prep Room | fume hood - improper use (not to be used for storage) | B | Caretaker | | Details |
| | 114 - Chemical Prep Room | chemicals or household cleaners not properly labelled | B | Caretaker | | Details |
| | Hallway | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Boiler | guarding or shielding not in place | A | Caretaker | | Details |
| | Hallway | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Exit 14 | paint flaking, chipping, possible lead exposure | A | Caretaker | | Details |
| | Exit 14 | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | 173 - Cafeteria | combustible material being displayed that is not fire rated/treated | B | | | Details |
| | Hallway | ceiling damaged (specify) | A | Caretaker | | Details |
| | Exit 8 | paint flaking, chipping, possible lead exposure | A | Caretaker | | Details |
| | prep room | improper storage (ie: not secured, not venting) | B | Caretaker | | Details |
| | 104 | lighting in need of repair (maintenance issue) | A | Caretaker | | Details |
| | 104 | exposed wiring/damaged cord/ground pin missing | A | Caretaker | | Details |
| | Staff Off | egress blocked or insufficient path (doorway, hallway or stairwell) | B | Caretaker | | Details |
| | W06 | ceiling damaged (specify) | A | Caretaker | | Details |
| | W06 | exposed wiring/damaged cord/ground pin missing | A | Caretaker | | Details |
| | W08 | ceiling damaged (specify) | A | Caretaker | | Details |
| | 109 | ceiling damaged (specify) | A | Caretaker | | Details |
| | 109 | receptacle/light switch (specify) | A | Caretaker | | Details |
| | 107 | lighting in need of repair (maintenance issue) | A | Caretaker | | Details |
| | 107 | receptacle/light switch (specify) | A | Caretaker | | Details |
| | 105 | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | 105 | receptacle/light switch (specify) | A | Caretaker | | Details |
| | 105 | ceiling damaged (specify) | A | Caretaker | | Details |
| | 105 | door/access door (specify) | A | Caretaker | | Details |
| | W05 | ceiling damaged (specify) | A | Caretaker | | Details |
| | 112 | ceiling damaged (specify) | A | Caretaker | | Details |
| | Exit 13 | door/access door (specify) | A | Caretaker | | Details |
| | Exit 13 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | | Details |
| | Hallway | paint flaking, chipping, possible lead exposure | A | Caretaker | | Details |
| | Boys' WR | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | | | Details |
| | Hallway | ceiling damaged (specify) | A | Caretaker | | Details |
| | 175 - Auto Shop | gas cylinder not secured | B | Caretaker | | Details |
| | 175 - Auto Shop | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | 175 - Auto Shop | improper storage (ie: not secured, not venting) | B | Caretaker | | Details |
| | 175 - Auto Shop | safety equipment and systems are not accessible, blocked or damaged (ie; fire pull station, fire hose, panel, gas feed, water shut off, blocked breakers) | B | Caretaker | | Details |
| | M 3 Mechanical room C | inspections not up to date (specify equipment) | B | Caretaker | | Details |
| | M 3 Mechanical room C | fire extinguisher not adequately charged or mounted | A | Caretaker | | Details |
| | Dark Room | ladder is constructed of wood/paint | A | Caretaker | | Details |
| | Dark Room | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | | Details |
| | Dark Room | fire extinguisher not adequately charged or mounted | A | Caretaker | | Details |
| | W08 | ceiling damaged (specify) | A | Caretaker | | Details |
| | W02 | egress blocked or insufficient path (doorway, hallway or stairwell) | B | Caretaker | | Details |
| | W14 | improper storage (ie: not secured, not venting) | B | Caretaker | | Details |
| | 114 - Chemical Prep Room | inspections not up to date (specify equipment) | B | Caretaker | | Details |
| | 114 - Chemical Prep Room | carts for transporting chemicals do not have 4 sides | B | Caretaker | | Details |
| | 114 - Chemical Prep Room | PPE - personal protective equipment not available | B | Caretaker | | Details |
| | 114 - Chemical Prep Room | fume hood - improper use (not to be used for storage) | B | Caretaker | | Details |
| | 114 - Chemical Prep Room | inspections not up to date (specify equipment) | B | Caretaker | | Details |
| | N01 | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | Exit 2 | ceiling damaged (specify) | A | Caretaker | | Details |
| | Gym Equipment Rooms | panel (specify) | A | Caretaker | | Details |
| | Gym Equipment Rooms | ceiling tiles missing/loose | A | Caretaker | | Details |
| | M8 - beside W22 | insufficient means of communication (ie: PA, radio, etc.) | B | Caretaker | | Details |
| | 175 - Auto Shop | eyewash station required or in need of repair (specify) | A | Caretaker | | Details |
| | 175 - Auto Shop | improper storage of flammable/combustible material | B | Caretaker | | Details |
| | 175 - Auto Shop | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | 175 - Auto Shop | microwave stickers missing | B | Caretaker | | Details |
| | M2 - up stair/ladder beside 166 | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | | Details |
| | prep room | PPE - personal protective equipment not available | B | Caretaker | | Details |
| | prep room | spill procedures are not posted | B | Principal | | Details |
| | prep room | NO FOOD & DRINK Sticker - not present or not being observed | B | Principal | | Details |
| | prep room | fume hood - improper use (not to be used for storage) | B | Caretaker | | Details |
| | prep room | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | prep room | egress blocked or insufficient path (doorway, hallway or stairwell) | B | Caretaker | | Details |
| | Hallway | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Hallway | ceiling damaged (specify) | A | Caretaker | | Details |
| | 168 - Wood Shop | anti-slip strips missing | B | Caretaker | | Details |
| | 168 - Wood Shop | anti-slip strips missing | B | Caretaker | | Details |
| | 202C | furniture being brought in from home | B | Caretaker | | Details |
| | 202A | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Caretaker | | Details |
| | Library Office | furniture being brought in from home | B | Caretaker | | Details |
| | 147 - Cooking | lighting in need of repair (maintenance issue) | A | Caretaker | | Details |
| | 147 - Cooking | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | | Details |
| | 136 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | | Details |
| | Hallway | ceiling damaged (specify) | A | Caretaker | | Details |
| | Hallway | ceiling damaged (specify) | A | Caretaker | | Details |
| | 167 | ceiling tiles missing/loose | A | Caretaker | | Details |
| | 158 | ceiling damaged (specify) | A | Caretaker | | Details |
| | M2 - up stair/ladder beside 166 | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | | Details |
| | Exit 4 | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Boiler room 1st floor | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | | Details |
| | Boiler room 1st floor | guarding or shielding not in place | A | Caretaker | | Details |
| | Boiler room 1st floor | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | | Details |
| | M2 - up stair/ladder beside 166 | lighting in need of repair (maintenance issue) | A | Caretaker | | Details |