| Date Inspected | Location in School | Health & Safety Issue Observed | Class | Action Taken By | Date Action Taken | Details |
| | Grounds | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | | Details |
| | Court Yard | clogged drain | A | Caretaker | | Details |
| | Storage | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | | Details |
| | Exit 2 | door/access door (specify) | A | Caretaker | | Details |
| | Seminar Room | ceiling damaged (specify) | A | Caretaker | | Details |
| | Library Work Room | unable to inspect (specify why if possible) | B | Caretaker | | Details |
| | M-7 above girls' change room of gym A | ladder not to standard (specify) | A | Caretaker | | Details |
| | Gym-Double | paint flaking, chipping, possible lead exposure | A | Caretaker | | Details |
| | Hallway | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Guidance Center | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | | Details |
| | Guidance Center | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Hallway | lighting in need of repair (maintenance issue) | A | Caretaker | | Details |
| | Hallway | ceiling damaged (specify) | A | Caretaker | | Details |
| | M-6 South | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | Boiler Room | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | | Details |
| | Boiler Room | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | | Details |
| | Boiler Room | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | | Details |
| | Boiler Room | insulation - required or in need of repair | A | Caretaker | | Details |
| | Boiler Room | guarding or shielding not in place | A | Caretaker | | Details |
| | Boiler Room | equipment damaged or improperly stored (specify) | B | Caretaker | | Details |
| | Boiler Room | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | | Details |
| | Boiler Room | portable ladder - damaged or not securely stored | A | Caretaker | | Details |
| | Boiler Room | insulation - required or in need of repair | A | Caretaker | | Details |
| | M-2 in Courtyard | door/access door (specify) | A | Caretaker | | Details |
| | Hallway | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Hallway | ceiling tiles missing/loose | A | Caretaker | | Details |
| | prep room | WHMIS labels missing on cylinders | B | Principal | | Details |
| | M-3 by 270 | unable to inspect (specify why if possible) | A | Principal | | Details |
| | 284 Wood Shop | fire extinguisher not adequately charged or mounted | A | Caretaker | | Details |
| | Stage | trip hazard (i.e. flooring, other materials) | A | Principal | | Details |
| | Stage | portable ladder - damaged or not securely stored | A | Caretaker | | Details |
| | Auditorium | furniture unsafe - requires repair | A | Caretaker | | Details |
| | Gym-Double | insufficient means of communication (ie: PA, radio, etc.) | B | Principal | | Details |
| | Gym-Single | insufficient means of communication (ie: PA, radio, etc.) | B | Principal | | Details |
| | 284 Wood Shop | insufficient means of communication (ie: PA, radio, etc.) | B | Principal | | Details |
| | 262 Auto Shop | insufficient means of communication (ie: PA, radio, etc.) | B | Principal | | Details |
| | 170 Prep Room | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | | Details |
| | M-4 across caf. above gym C change rooms | eyewash station required or in need of repair (specify) | A | Caretaker | | Details |
| | 258 Dark Room | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | | Details |
| | 258 Dark Room | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | | Details |
| | 223 Cosmo Shop | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | | Details |
| | Gym-Single | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | | Details |
| | 284 Wood Shop | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | | Details |
| | 284 Wood Shop | housekeeping, clutter, dust or dirt | B | Principal | | Details |
| | 170 Prep Room | eyewash station required or in need of repair (specify) | A | Caretaker | | Details |
| | 170 Prep Room | inspections not up to date (specify equipment) | B | Principal | | Details |
| | 170 Prep Room | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Fan Room on roof | unable to inspect (specify why if possible) | B | Caretaker | | Details |
| | General | workplace inspection hazards (E-WIP) not addressed | B | Caretaker | | Details |
| | 256/258 | anti-slip strips missing | B | Principal | | Details |
| | M-1 Boiler Rooms | paint flaking, chipping, possible lead exposure | A | Caretaker | | Details |
| | Hallway | ceiling damaged (specify) | A | Caretaker | | Details |
| | 103 | leaking/pooling/ponding of liquid (specify liquid and source if possible) | A | Caretaker | | Details |
| | 100 | leaking/pooling/ponding of liquid (specify liquid and source if possible) | A | Caretaker | | Details |
| | 101 Prep Room | window covering damaged/in need of repair | A | Caretaker | | Details |
| | 202 | door/access door (specify) | A | Caretaker | | Details |
| | 220 Copy Room | drain (specify) | A | Caretaker | | Details |
| | Exit 4 | ceiling tiles missing/loose | A | Caretaker | | Details |
| | M-2 in Courtyard | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | | Details |
| | 262 Auto Shop | anti-slip strips missing | B | Principal | | Details |
| | 110 | ceiling tiles missing/loose | A | Caretaker | | Details |
| | 112 | ceiling tiles missing/loose | A | Caretaker | | Details |
| | 262 Auto Shop | anti-slip strips missing | B | Principal | | Details |
| | Boiler Room | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | | Details |
| | Hallway | ceiling tiles missing/loose | A | Caretaker | | Details |
| | Hallway | lighting in need of repair (maintenance issue) | A | Caretaker | | Details |
| | 154 | window covering recommended on 1st floor (emergency lockdown procedures) | B | Caretaker | | Details |
| | 150 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | | Details |
| | 150 | window damaged, in need of repair (specify) | A | Caretaker | | Details |
| | 152 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | | Details |
| | Hallway | window damaged, in need of repair (specify) | A | Caretaker | | Details |
| | 106 | window damaged, in need of repair (specify) | A | Caretaker | | Details |
| | 104/106 Prep Room | paint flaking, chipping, possible lead exposure | A | Caretaker | | Details |
| | Office - Math | window damaged, in need of repair (specify) | A | Caretaker | | Details |
| | 100 | paint flaking, chipping, possible lead exposure | A | Caretaker | | Details |
| | 101 | window damaged, in need of repair (specify) | A | Caretaker | | Details |
| | 101 | paint flaking, chipping, possible lead exposure | A | Caretaker | | Details |
| | 103 | paint flaking, chipping, possible lead exposure | A | Caretaker | | Details |
| | 103 | receptacle/light switch (specify) | A | Caretaker | | Details |
| | Boiler Room | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | | Details |
| | Exit 8 | ceiling tiles missing/loose | A | Caretaker | | Details |
| | prep room | ceiling tiles missing/loose | A | Caretaker | | Details |
| | 284 Wood Shop | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |
| | General | insufficient means of communication (ie: PA, radio, etc.) | B | Principal | | Details |
| | Staff Lounge | household cleaners present (not TDSB approved) | B | Caretaker | | Details |
| | 203 | insufficient means of communication (ie: PA, radio, etc.) | B | Principal | | Details |
| | Office - Vice Principal | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | | Details |
| | Office - Main | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | | Details |
| | Office - Main | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Caretaker | | Details |
| | Office - Main | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Caretaker | | Details |
| | Social Worker Room (in Main Office) | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Caretaker | | Details |
| | General | insufficient means of communication (ie: PA, radio, etc.) | B | Caretaker | | Details |
| | 202 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Caretaker | | Details |
| | 204 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Caretaker | | Details |
| | 203 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Caretaker | | Details |
| | 201 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Caretaker | | Details |
| | 170 Prep Room | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | A | Caretaker | | Details |
| | 204 | insufficient means of communication (ie: PA, radio, etc.) | B | Caretaker | | Details |
| | 201 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Caretaker | | Details |
| | Wellness Room | chemicals or household cleaners not properly labelled | B | Caretaker | | Details |
| | 206 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | | Details |
| | Hallway | panel (specify) | A | Caretaker | | Details |
| | 170 Prep Room | ceiling tiles missing/loose | A | Caretaker | | Details |
| | 170 Prep Room | inspections not up to date (specify equipment) | B | Caretaker | | Details |
| | 284 Wood Shop | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | | Details |
| | 284 Wood Shop | emergency exit sign (specify) | A | Caretaker | | Details |
| | 262 Auto Shop | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | | Details |
| | 284 Wood Shop | emergency exit door - mechanical malfunction on exit door | A | Caretaker | | Details |
| | M-4 across caf. above gym C change rooms | eyewash station required or in need of repair (specify) | A | Caretaker | | Details |
| | Staff Room | Names and Locations of Certified First Aiders on site | B | Caretaker | | Details |
| | Fan Room on roof | unable to inspect (specify why if possible) | B | Caretaker | | Details |
| | M-1 Boiler Rooms | eyewash station required or in need of repair (specify) | A | Caretaker | | Details |
| | Staff Room | trip hazard (i.e. flooring, other materials) | A | Caretaker | | Details |