Health and Safety (H&S) workplace inspections are conducted every month in all of our 582 operating schools. Below you can find the H&S reports for your school, for the 2019-2020 and 2020-2021 school years.  More information and Frequently Asked Questions

Date InspectedLocation in SchoolHealth & Safety Issue ObservedClassAction Taken ByDate Action TakenDetails
09/25/19318B Chemical Prep Roomeyewash station required or in need of repair (specify)ACaretaker09/27/19Details
10/31/19102exposed wiring/damaged cord/ground pin missingACaretaker11/11/19Details
10/31/19103exposed wiring/damaged cord/ground pin missingACaretaker11/11/19Details
10/31/19318B Chemical Prep Roomfume hood - improper use (not to be used for storage)BCaretaker11/11/19Details
10/31/19Stairsdoor/access door (specify)ACaretaker11/11/19Details
10/31/19318B Chemical Prep Roomeyewash station required or in need of repair (specify)ACaretaker11/11/19Details
10/31/19318B Chemical Prep Roomeyewash station required or in need of repair (specify)ACaretaker11/11/19Details
10/31/19104 Gym Southfire exit route sign (yellow TDSB) - not posted / requires updatingBCaretaker11/11/19Details
10/31/19103ACM - insulation material damaged, possible ACMA1Caretaker11/11/19Details
10/31/19Fan Room 52ACM - insulation material damaged, possible ACMA1Caretaker11/11/19Details
10/31/19102damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker11/11/19Details
10/31/1934E Pool Filter Roomceiling tiles missingACaretaker11/11/19Details
11/19/19Fan Room above 30 storage roomguarding or shielding not in placeACaretaker11/30/19Details
11/19/19Hallwayceiling damaged (specify)ACaretaker11/30/19Details
11/19/19Fan Room end of North Gym galleryguarding or shielding not in placeACaretaker11/30/19Details
11/19/19Fan Room 52extinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/30/19Details
11/19/1938D Mechanical Roomextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/30/19Details
11/19/19Fan Room end of North Gym galleryextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/30/19Details
11/19/19Gym Officeextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/30/19Details
11/19/19Fan Room above 104Cextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/30/19Details
11/19/19Fan Room above 303extinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/30/19Details
11/19/19318C Chemical Storage Roomextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/30/19Details
11/19/19Stairsinappropriate storage of materials/furniture/shelving, or clutterBCaretaker11/30/19Details
11/19/1966B Caretakerequipment damaged or not securedBCaretaker11/30/19Details
11/19/19Office - Main 121ventilation (specify)ACaretaker11/30/19Details
11/19/19Gym OfficemouldBCaretaker11/30/19Details
11/19/19Auditoriumextension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCaretaker11/30/19Details
11/19/19Hallwayceiling damaged (specify)ACaretaker11/30/19Details
11/19/19Stairsceiling damaged (specify)ACaretaker11/30/19Details
11/19/19Gym Officeceiling damaged (specify)ACaretaker11/30/19Details
11/19/19Hallwayceiling damaged (specify)ACaretaker11/30/19Details
11/19/19Fan Room above 104Cguarding or shielding not in placeACaretaker11/30/19Details
12/29/1955 Weight Roomsceiling tiles missingACaretaker01/12/20Details
12/29/1959 Storageceiling damaged (specify)ACaretaker01/12/20Details
12/29/1941window damaged, in need of repair (specify)ACaretaker01/12/20Details
12/29/1934E Pool Filter Roomleaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker01/12/20Details
12/29/1951 Outside Team Rmdamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker01/12/20Details
12/29/19Fan Room above 104Cdamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker01/12/20Details
12/29/1955 Weight Roomsventilation (specify)ACaretaker01/12/20Details
12/29/1960 Officefire exit route sign (yellow TDSB) - not posted / requires updatingBCaretaker01/12/20Details
12/29/1966B Caretakerequipment damaged or not securedBCaretaker01/12/20Details
12/29/1935 Chemical Storage Roomchemicals or household cleaners not properly labelledBCaretaker01/12/20Details
12/29/1934 F caretarer/chlorine rmimproper storage (ie: not secured, not venting)BCaretaker01/12/20Details
12/29/1951 Instr Officedoor/access door (specify)ACaretaker01/12/20Details
12/29/1934E Pool Filter Roomtrip hazard (i.e. flooring, other materials)ACaretaker01/12/20Details
12/29/19Fan Room above 104Ctrip hazard (i.e. flooring, other materials)ACaretaker01/12/20Details
12/29/1940C Electrical Roomguarding or shielding not in placeACaretaker01/12/20Details
12/29/19Fan Room above 104Cguarding or shielding not in placeACaretaker01/12/20Details
12/29/1963unable to inspect (specify why if possible)BCaretaker01/12/20Details
12/29/1934E Pool Filter Roominsulation - required or in need of repairACaretaker01/12/20Details
12/29/19Fan Room across 318extinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/12/20Details
12/29/1934E Pool Filter Roomextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/12/20Details
12/29/1938D Mechanical Roomextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/12/20Details
12/29/1985 Pump Roomextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/12/20Details
12/29/19318C Chemical Storage Roomextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/12/20Details
12/29/1949 Slop Sink/ Receivingextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/12/20Details
12/29/19Fan Room end of North Gym galleryextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/12/20Details
12/29/19Fan Room above 303extinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/12/20Details
12/29/1964inappropriate storage of materials/furniture/shelving, or clutterBCaretaker01/12/20Details
02/13/20Fan Room above 104Cguarding or shielding not in placeACaretaker02/26/20Details
02/13/20Fan Room above 104Cinappropriate storage of materials/furniture/shelving, or clutterBCaretaker02/26/20Details
03/26/2034E Pool Filter Roomceiling damaged (specify)ACaretaker05/04/20Details
03/26/20Fan Room above 104Cunable to inspect (specify why if possible)BCaretaker05/04/20Details
03/26/2038 Boiler Roomunable to inspect (specify why if possible)BCaretaker05/04/20Details
03/26/20318B Chemical Prep Roominspections not up to date (specify equipment)BCaretaker05/04/20Details
03/26/20Fan rm by 5CACM - insulation material damaged, possible ACMA1Caretaker05/04/20Details
03/26/20312damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker05/04/20Details
03/26/20312paint flaking, chipping, possible lead exposureACaretaker05/04/20Details
06/03/20111Health & Safety bulletin board - required items are missing or outdated (be specific)BCaretaker06/12/20Details
06/03/20318B Chemical Prep Roominspections not up to date (specify equipment)BCaretaker06/12/20Details
06/03/20119exposed wiring/damaged cord/ground pin missingACaretaker06/12/20Details
07/24/20Rooffixed ladder required, or not to code (specify)ACaretaker07/24/20Details
07/24/20Roofdamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker07/24/20Details
08/31/20Groundsuneven surface - driveway, parking lot, walkway, or otherACaretaker09/02/20Details
08/31/20Groundsuneven surface - driveway, parking lot, walkway, or otherACaretaker09/02/20Details
08/31/20Boiler Room 38unable to inspect (specify why if possible)BCaretaker09/02/20Details
09/17/20South Gym Galleryceiling damaged (specify)ACaretaker09/18/20Details
09/17/20South Gymceiling damaged (specify)ACaretaker09/18/20Details
09/17/20206A Officeceiling damaged (specify)ACaretaker09/18/20Details
09/17/20Hallwayceiling damaged (specify)ACaretaker09/18/20Details
09/17/20211paint flaking, chipping, possible lead exposureACaretaker09/18/20Details
09/17/20Exit 2paint flaking, chipping, possible lead exposureACaretaker09/18/20Details
09/17/20212temperature does not meet TDSB GuidelineACaretaker09/18/20Details
09/17/20Girl's washroomexposed wiring/damaged cord/ground pin missingACaretaker09/18/20Details
09/17/20223trip hazard (i.e. flooring, other materials)ACaretaker09/18/20Details
09/17/2040B Mechanical Roomleaking/pooling/ponding of water or liquid (be as specific as possible)ACaretaker09/18/20Details
09/17/20Boiler Room 38inappropriate storage of materials/furniture/shelving, or clutterBCaretaker09/18/20Details
09/17/20Stair 3ceiling tiles missingACaretaker09/18/20Details
09/17/20Girl's washroomceiling tiles missingACaretaker09/18/20Details
10/02/20Gym Officefurniture being brought in from homeBCaretaker10/19/20Details
10/02/2034E Pool Filter Roomleaking/pooling/ponding of water or liquid (be as specific as possible)ACaretaker10/19/20Details
10/02/20Fan Room across 214fire extinguisher not adequately charged or mountedACaretaker10/19/20Details
10/02/2034 B Staffwash roomShared kitchen appliances are present /in useBCaretaker10/19/20Details
10/02/20112Shared kitchen appliances are present /in useBCaretaker10/19/20Details
11/06/20Guidance Office - Three additional officesunable to inspect (specify why if possible)BCaretaker11/21/20Details
11/06/20109 Computer Labventilation (specify)ACaretaker11/21/20Details
11/06/20218ceiling damaged (specify)ACaretaker11/21/20Details
11/06/20219ceiling damaged (specify)ACaretaker11/21/20Details
11/06/20213 Officeceiling tiles missingACaretaker11/21/20Details
11/06/20Guidance Office - Three additional officesceiling tiles missingACaretaker11/21/20Details
11/06/20106baseboard/radiator heater cover missingACaretaker11/21/20Details
11/17/20Foyerceiling tiles missingACaretaker11/21/20Details
11/17/20Hallwayceiling damaged (specify)ACaretaker11/21/20Details
11/17/20Office - Vice Principalceiling damaged (specify)ACaretaker11/21/20Details
11/17/20Auditorium Foyerceiling damaged (specify)ACaretaker11/21/20Details
11/17/20Stairsceiling damaged (specify)ACaretaker11/21/20Details
11/17/20Hallwayceiling damaged (specify)ACaretaker11/21/20Details
11/17/2038Bequipment damaged or not securedBCaretaker11/21/20Details
11/17/2066B Caretakerequipment damaged or not securedBCaretaker11/21/20Details
11/17/20Exitdoor/access door (specify)ACaretaker11/21/20Details
11/17/20Fan Room 38Dextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/21/20Details
11/17/20Fan Room above 104Cextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/21/20Details
11/17/20Hallwayinappropriate storage of materials/furniture/shelving, or clutterBCaretaker11/21/20Details
11/17/2038 Boiler Roominappropriate storage of materials/furniture/shelving, or clutterBCaretaker11/21/20Details
12/17/20Boiler Room 38unable to inspect (specify why if possible)BCaretaker01/05/21Details
12/17/2038D Mechanical Roominsulation - required or in need of repairACaretaker01/05/21Details
12/17/2038D Mechanical Roomextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/05/21Details
12/17/20Stairsextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/05/21Details
12/17/20Stairsextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/05/21Details
12/17/20318C Chemical Storage Roomextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker01/05/21Details
12/17/2041ACM - tiles broken/damaged, possible ACMACaretaker01/05/21Details
12/17/20HallwayACM - tiles broken/damaged, possible ACMACaretaker01/05/21Details
12/17/20318C Chemical Storage Roomfume hood - improper use (not to be used for storage)BCaretaker01/05/21Details
12/17/20Fan Room above 104Cinappropriate storage of materials/furniture/shelving, or clutterBCaretaker01/05/21Details
12/17/2051 Instr Officeinappropriate storage of materials/furniture/shelving, or clutterBCaretaker01/05/21Details
12/17/20222Atrip hazard (i.e. flooring, other materials)ACaretaker01/05/21Details
12/17/20Fan Room above 104Ctrip hazard (i.e. flooring, other materials)ACaretaker01/05/21Details
12/17/2050trip hazard (i.e. flooring, other materials)ACaretaker01/05/21Details
12/17/2065trip hazard (i.e. flooring, other materials)ACaretaker01/05/21Details
12/17/20222Adoor/access door (specify)ACaretaker01/05/21Details
12/17/2034 F caretarer/chlorine rmimproper storage (ie: not secured, not venting)BCaretaker01/05/21Details
12/17/20318C Chemical Storage Roomchemicals or household cleaners not properly labelledBCaretaker01/05/21Details
12/17/2066B Caretakerequipment damaged or not securedBCaretaker01/05/21Details
12/17/2065fire exit route sign (yellow TDSB) - not posted / requires updatingBCaretaker01/05/21Details
12/17/2048 Caretakermicrowave stickers missingBCaretaker01/05/21Details
12/17/20318C Chemical Storage Roomventilation (specify)ACaretaker01/05/21Details
12/17/20222Adamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker01/05/21Details
12/17/2051 Outside Team Rmdamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker01/05/21Details
12/17/2051 Outside Team Rmdamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker01/05/21Details
12/17/2047 Caretakerdamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker01/05/21Details
12/17/2041damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker01/05/21Details
12/17/2051 Outside Team Rmdamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker01/05/21Details
12/17/2051 Outside Team Rmpaint flaking, chipping, possible lead exposureACaretaker01/05/21Details
12/17/2051 Outside Team Rmwindow damaged, in need of repair (specify)ACaretaker01/05/21Details
12/17/2040 Cafeteriaceiling damaged (specify)ACaretaker01/05/21Details
12/17/20Hallwayceiling damaged (specify)ACaretaker01/05/21Details
12/17/20Fan Room above 104Cceiling damaged (specify)ACaretaker01/05/21Details
12/17/2055 Weight Roomsceiling damaged (specify)ACaretaker01/05/21Details
12/17/2058ceiling damaged (specify)ACaretaker01/05/21Details
12/17/2055 Weight Roomsceiling tiles missingACaretaker01/05/21Details
12/17/2040 Cafeteriaceiling tiles missingACaretaker01/05/21Details
01/07/2134 Poolunable to inspect (specify why if possible)BCaretaker01/07/21Details
02/25/21315door/access door (specify)ACaretaker03/08/21Details
02/25/21Upper Part of Auditoriumpaint flaking, chipping, possible lead exposureACaretaker03/08/21Details
02/25/21Stair 6damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker03/08/21Details
02/25/21318C Chemical Storage Roomimproper storage (ie: not secured, not venting)BCaretaker03/08/21Details
02/25/21Hallwaypaint flaking, chipping, possible lead exposureACaretaker03/08/21Details
02/25/21Stair 5paint flaking, chipping, possible lead exposureACaretaker03/08/21Details
02/25/21318A Officepaint flaking, chipping, possible lead exposureACaretaker03/08/21Details
02/25/21319paint flaking, chipping, possible lead exposureACaretaker03/08/21Details
02/25/21320 Officepaint flaking, chipping, possible lead exposureACaretaker03/08/21Details
02/25/21321paint flaking, chipping, possible lead exposureACaretaker03/08/21Details
02/25/21Stair 5ceiling tiles missingACaretaker03/08/21Details
02/25/21Hallwayexposed wiring/damaged cord/ground pin missingACaretaker03/08/21Details
02/25/21Boy's Washroomexposed wiring/damaged cord/ground pin missingACaretaker03/08/21Details
02/25/21318ceiling tiles missingACaretaker03/08/21Details
02/25/21319ceiling tiles missingACaretaker03/08/21Details
03/05/21312insulation - required or in need of repairACaretaker04/21/21Details
03/05/21308insulation - required or in need of repairACaretaker04/21/21Details
03/05/21303 Officeequipment damaged or not securedBCaretaker04/21/21Details
03/05/21Fan Room across 318insufficient means of communication (ie: PA, radio, etc.)BCaretaker04/21/21Details
03/05/21Office - Main 121air - return/supply (specify)ACaretaker04/21/21Details
03/05/21302extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCaretaker04/21/21Details
03/05/21303 Officebleach is present, where not permitted or not properly storedBCaretaker04/21/21Details
04/05/21221extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCaretaker04/28/21Details
04/05/21318B Chemical Prep Roominsufficient means of communication (ie: PA, radio, etc.)BCaretaker04/28/21Details
04/05/21318B Chemical Prep Roomspill procedures are not postedBCaretaker04/28/21Details
04/05/21318B Chemical Prep Roombroken glass container is required in science storage/prep roomBCaretaker04/28/21Details
04/05/21220extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCaretaker04/28/21Details
04/05/21318B Chemical Prep Roomcarts for transporting chemicals do not have 4 sidesBCaretaker04/28/21Details
05/06/2134E Pool Filter Roomleaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker05/26/21Details
05/06/21108extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCaretaker05/26/21Details
05/06/21109 Libraryextension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCaretaker05/26/21Details
05/06/21109 Librarydisplay(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)BCaretaker05/26/21Details
05/06/21318B Chemical Prep Roomcarts for transporting chemicals do not have 4 sidesBCaretaker05/26/21Details
06/09/21119receptacle/light switch (specify)ACaretaker06/18/21Details
06/09/21118equipment damaged or not securedBCaretaker06/18/21Details