Health and Safety (H&S) workplace inspections are conducted every month in all of our 582 operating schools. Below you can find the H&S reports for your school, for the 2019-2020 and 2020-2021 school years.  More information and Frequently Asked Questions

Date InspectedLocation in SchoolHealth & Safety Issue ObservedClassAction Taken ByDate Action TakenDetails
09/30/19162microwave stickers missingBCaretaker10/02/19Details
09/30/19170Amicrowave stickers missingBCaretaker10/02/19Details
09/30/19Greenhouseunable to inspect (specify why if possible)BPrincipal10/01/19Details
09/30/19166inappropriate storage of materials/furniture/shelving, or clutterBCaretaker10/02/19Details
10/26/19165bleach is present, where not permitted or not properly storedBPrincipal10/28/19Details
10/26/19Change Roomwindow damaged, in need of repair (specify)ACaretaker10/28/19Details
10/26/19Exitdoor/access door (specify)ACaretaker10/28/19Details
11/05/19117window covering damaged/in need of repairACaretaker11/14/19Details
11/05/19107ventilation (specify)ACaretaker11/14/19Details
12/30/19Fan room - above stage rightunable to inspect (specify why if possible)BPrincipal01/06/20Details
12/30/19208ceiling damaged (specify)ACaretaker01/06/20Details
12/30/19166ceiling damaged (specify)ACaretaker01/06/20Details
12/30/19166ceiling damaged (specify)ACaretaker01/06/20Details
12/30/19Caretaker storagemouldBCaretaker01/06/20Details
12/30/19Roofunable to inspect (specify why if possible)BPrincipal01/06/20Details
01/26/20203 Chemical Storage Roombucket of sand is required for class D firesBPrincipal01/27/20Details
01/26/20Boiler Roomeyewash station required or in need of repair (specify)ACaretaker01/28/20Details
01/26/20205microwave stickers missingBCaretaker01/28/20Details
01/26/20209ceiling damaged (specify)ACaretaker01/28/20Details
01/26/20205ceiling tiles missingACaretaker01/28/20Details
01/26/20211ceiling tiles missingACaretaker01/28/20Details
01/26/20203 Chemical Storage Roombroken glass container is required in science storage/prep roomBPrincipal01/27/20Details
02/17/20Hallwayceiling tiles missingACaretaker02/21/20Details
02/17/20228ceiling tiles missingACaretaker02/21/20Details
02/17/20Hallwayceiling tiles missingACaretaker02/21/20Details
02/17/20Fan room - 222guarding or shielding not in placeACaretaker02/21/20Details
06/18/20Office - Mainguarding or shielding not in placeAPrincipal07/09/20Details
07/09/20Hallwayceiling tiles missingACaretaker07/09/20Details
07/09/20Hallwayceiling damaged (specify)ACaretaker07/09/20Details
07/09/20slop sinkceiling damaged (specify)ACaretaker07/09/20Details
07/09/20218ceiling damaged (specify)ACaretaker07/09/20Details
07/09/20Transformer Enclosurevegetation (please specify concern)ACaretaker07/09/20Details
09/18/20Hallwayceiling tiles missingACaretaker09/28/20Details
09/18/20170Aceiling damaged (specify)ACaretaker09/28/20Details
09/18/20Hallwayceiling damaged (specify)ACaretaker09/28/20Details
09/18/20168lighting in need of repair (maintenance issue)ACaretaker09/28/20Details
09/18/20114extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal09/21/20Details
09/18/20Fan room - above stage rightextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker09/28/20Details
10/29/20165temperature does not meet TDSB GuidelineACaretaker10/30/20Details
11/09/20Computer Roomegress blocked or insufficient path (doorway, hallway or stairwell)BPrincipal11/09/20Details
11/09/20111receptacle/light switch (specify)ACaretaker11/10/20Details
11/09/20101 Libraryceiling damaged (specify)ACaretaker11/10/20Details
11/09/20Hallwayceiling tiles missingACaretaker11/10/20Details
11/09/20Computer Roomceiling tiles missingACaretaker11/10/20Details
11/09/20Exit 1ceiling tiles missingACaretaker11/10/20Details
11/30/20Hallwayfire separating doors in hallways/corridors being propped open (not classroom doors)BPrincipal12/04/20Details
01/24/21203ceiling tiles missingACaretaker01/26/21Details
01/24/21203 Chemical Storage Roomspill kit or bucket of sand is not availableBPrincipal01/25/21Details
01/24/21203 Chemical Storage Roomspill procedures are not postedBPrincipal01/25/21Details
01/24/21203 Chemical Storage Roomimproper storage - all chemicals to be stored below 6ftBPrincipal01/25/21Details
01/24/21160 Wood Shopequipment damaged or not securedBPrincipal01/25/21Details
01/24/21203 Chemical Storage RoomPPE - personal protective equipment not availableBPrincipal01/25/21Details
01/24/21160 Wood Shopextension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal01/25/21Details
01/24/21205extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal01/25/21Details
01/24/21209extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal01/25/21Details
01/24/21Hallwayceiling tiles missingACaretaker01/26/21Details
01/24/21225Aceiling tiles missingACaretaker01/26/21Details
01/24/21207ceiling tiles missingACaretaker01/26/21Details
01/24/21211ceiling tiles missingACaretaker01/26/21Details
01/24/21209ceiling tiles missingACaretaker01/26/21Details
02/15/21160 Wood Shopextension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCaretaker02/18/21Details
02/15/21Hallwayceiling damaged (specify)ACaretaker02/18/21Details
02/15/21216ceiling damaged (specify)ACaretaker02/18/21Details
02/15/21230ceiling tiles missingACaretaker02/18/21Details
02/15/21224extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCaretaker02/18/21Details
03/18/21160 Wood Shopimproper storage (ie: not secured, not venting)BCaretaker03/18/21Details
04/27/21158ceiling damaged (specify)ACaretaker04/28/21Details
04/27/21152receptacle/light switch (specify)ACaretaker04/28/21Details
04/27/21152damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker04/28/21Details
04/27/21156ceiling tiles missingACaretaker04/28/21Details
04/30/21Exit 2egress blocked or insufficient path (doorway, hallway or stairwell)BCaretaker05/31/21Details
04/30/21115Aair - return/supply (specify)ACaretaker05/31/21Details
04/30/21Fan room - above stage rightlighting in need of repair (maintenance issue)ACaretaker05/31/21Details
04/30/21Hallwayfire separating doors in hallways/corridors being propped open (not classroom doors)BCaretaker05/31/21Details