Date Inspected | Location in School | Health & Safety Issue Observed | Class | Action Taken By | Date Action Taken | Details |
09/14/23 | 326A Histoire | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 10/02/23 | Details |
09/14/23 | History office A | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 10/02/23 | Details |
09/14/23 | History Office B | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 10/02/23 | Details |
09/14/23 | 331A | lighting is insufficient for task in work area, room number and why | B | | | Details |
09/14/23 | 332 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 06/03/24 | Details |
09/14/23 | 230A Chemical Storage | lighting is insufficient for task in work area, room number and why | B | Principal | 05/02/24 | Details |
09/14/23 | 332A | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 10/02/23 | Details |
09/14/23 | 332 | door/access door (specify) | A | Principal | 10/02/23 | Details |
09/14/23 | 325 | receptacle/light switch (specify) | A | Caretaker | 06/03/24 | Details |
09/14/23 | 324 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 10/02/23 | Details |
09/14/23 | 331 | eyewash station required or in need of repair (specify) | A | Principal | 05/02/24 | Details |
10/02/23 | Library Office | chemicals or household cleaners not properly labelled | B | Principal | 06/06/24 | Details |
10/02/23 | 332A Chemical Prep Room | eyewash station required or in need of repair (specify) | A | Caretaker | 12/01/23 | Details |
10/02/23 | 331A | inspections not up to date (specify equipment) | B | Caretaker | 11/14/23 | Details |
10/02/23 | 331A | carts for transporting chemicals do not have 4 sides | B | Principal | | Details |
10/02/23 | Fan Room F | guarding or shielding not in place | A | Caretaker | 11/14/23 | Details |
10/02/23 | 331A | spill kit or bucket of sand is not available | B | Principal | 05/02/24 | Details |
10/02/23 | 206A | spill kit or bucket of sand is not available | B | Principal | 05/02/24 | Details |
10/02/23 | 206A | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 11/14/23 | Details |
10/02/23 | Fan Room G | guarding or shielding not in place | A | Caretaker | 11/14/23 | Details |
10/02/23 | 224 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 11/14/23 | Details |
10/02/23 | 225 | chemicals or household cleaners not properly labelled | B | Principal | 06/06/24 | Details |
10/02/23 | 226 | combustible material being displayed that is not fire rated/treated | | | | Details |
10/02/23 | 227 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 11/14/23 | Details |
10/02/23 | 228 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 11/14/23 | Details |
10/02/23 | 229A | inappropriate storage of materials/furniture/shelving, or clutter | B | Principal | 06/06/24 | Details |
10/02/23 | 229 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 11/14/23 | Details |
10/02/23 | 230 | inspections not up to date (specify equipment) | B | Caretaker | 11/14/23 | Details |
10/02/23 | 230 | fume hood - improper use (not to be used for storage) | B | Caretaker | 11/14/23 | Details |
10/02/23 | 332A Chemical Prep Room | spill kit or bucket of sand is not available | B | Principal | 05/02/24 | Details |
10/02/23 | 230A Chemical Storage | spill kit or bucket of sand is not available | B | Principal | 05/02/24 | Details |
10/02/23 | 231 | combustible material being displayed that is not fire rated/treated | A | Principal | 06/06/24 | Details |
11/13/23 | 136 | housekeeping, clutter, dust or dirt | B | Caretaker | 11/14/23 | Details |
11/13/23 | 136 | guarding or shielding not in place | A | Caretaker | 11/14/23 | Details |
11/13/23 | 136 | guarding or shielding not in place | A | Caretaker | 11/14/23 | Details |
11/13/23 | 136 | ceiling tiles missing/loose | A | Caretaker | 11/14/23 | Details |
11/13/23 | 136 | equipment damaged or improperly stored (specify) | B | Caretaker | 11/14/23 | Details |
11/13/23 | 136 | microwave stickers missing | B | Caretaker | 12/01/23 | Details |
11/13/23 | Boiler Room (2nd floor) | portable ladder - damaged or not securely stored | A | Caretaker | 11/14/23 | Details |
11/13/23 | 331A | carts for transporting chemicals do not have 4 sides | B | Principal | 05/02/24 | Details |
11/13/23 | Fan Room G | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 11/14/23 | Details |
11/13/23 | 206A | eyewash station required or in need of repair (specify) | A | Caretaker | 12/01/23 | Details |
11/13/23 | 206A | spill kit or bucket of sand is not available | B | Principal | 05/02/24 | Details |
11/13/23 | 206A | chemical storage areas are not clearly identified according TDSB Chemical Storage labelling guidelines. | A | Principal | 05/02/24 | Details |
11/13/23 | 206A | ceiling tiles missing/loose | A | Caretaker | 12/01/23 | Details |
11/13/23 | Fan Room H | emergency lighting damaged/missing | A | Caretaker | 11/14/23 | Details |
11/13/23 | Fan Room H | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 11/14/23 | Details |
11/13/23 | 230A Chemical Storage | improper storage - all chemicals to be stored below 6ft | A | Principal | 05/02/24 | Details |
11/13/23 | 331A | fume hood - improper use (not to be used for storage) | B | Caretaker | 11/14/23 | Details |
11/13/23 | 331A | ceiling tiles missing/loose | A | Caretaker | 11/14/23 | Details |
11/13/23 | Upper Fan Room | portable ladder - damaged or not securely stored | A | Caretaker | 11/14/23 | Details |
11/13/23 | mechanical room bsmt | eyewash station required or in need of repair (specify) | A | Caretaker | 11/14/23 | Details |
11/13/23 | 333 Drama Complex | ceiling damaged (specify) | A | Caretaker | 11/14/23 | Details |
11/13/23 | 319 | lighting in need of repair (maintenance issue) | A | Caretaker | 11/14/23 | Details |
11/13/23 | Stairwell 8 | ceiling tiles missing/loose | A | Caretaker | 11/14/23 | Details |
11/13/23 | Stairwell 8 | ceiling damaged (specify) | A | Caretaker | 11/14/23 | Details |
11/13/23 | Stairwell 8 | lighting in need of repair (maintenance issue) | A | Caretaker | 11/14/23 | Details |
11/13/23 | Stairwell 8 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 11/14/23 | Details |
11/13/23 | Stairwell 8 | paint flaking, chipping, possible lead exposure | A | Caretaker | 11/14/23 | Details |
11/13/23 | staff room | Joint Health & Safety Committee meeting minutes not posted (including names and contact numbers) | B | Principal | 05/02/24 | Details |
11/13/23 | Hallway | ceiling tiles missing/loose | A | Caretaker | 11/14/23 | Details |
12/12/23 | Pool Filter Room | door or stairwell not numbered properly (interior or exterior), (specify) | B | Caretaker | 01/02/24 | Details |
12/12/23 | Gym 3 | receptacle/light switch (specify) | A | Caretaker | 01/02/24 | Details |
12/12/23 | staff room | Workplace Inspection Form | B | Principal | 02/01/24 | Details |
01/08/24 | 207 | air - return/supply (specify) | A | Caretaker | 02/26/24 | Details |
01/08/24 | 208 | air - return/supply (specify) | A | Caretaker | 02/26/24 | Details |
01/08/24 | 209 | air - return/supply (specify) | A | Caretaker | 02/26/24 | Details |
02/08/24 | Boy's washroom | unable to inspect (specify why if possible) | B | Caretaker | 02/26/24 | Details |
02/08/24 | Girl's washroom | unable to inspect (specify why if possible) | B | Caretaker | 02/26/24 | Details |
03/01/24 | Fan Room F | guarding or shielding not in place | A | Caretaker | 03/13/24 | Details |
03/01/24 | Fan Room B | guarding or shielding not in place | A | Caretaker | 03/13/24 | Details |
03/01/24 | 319 | eyewash station required or in need of repair (specify) | A | Caretaker | 03/13/24 | Details |
03/01/24 | 319 | carts for transporting chemicals do not have 4 sides | B | Principal | 05/02/24 | Details |
03/01/24 | 217 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 05/02/24 | Details |
03/01/24 | 222 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 05/02/24 | Details |
03/01/24 | 215a | trip hazard (i.e. flooring, other materials) | A | Caretaker | 03/13/24 | Details |
03/01/24 | 215a | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 05/02/24 | Details |
03/01/24 | 135 Construction Tech | anti-slip strips missing | B | Principal | 05/02/24 | Details |
03/01/24 | 332A Chemical Prep Room | eyewash station required or in need of repair (specify) | A | Caretaker | 03/13/24 | Details |
04/09/24 | Boiler Room (2nd floor) | ladder not to standard (specify) | A | Caretaker | 04/15/24 | Details |
04/09/24 | 136 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 05/02/24 | Details |
04/09/24 | 109 practice room b | window covering damaged/in need of repair | A | Caretaker | 04/15/24 | Details |
04/09/24 | 109 practice room b | leaking/pooling/ponding of liquid (specify liquid and source if possible) | A | Caretaker | 04/15/24 | Details |
04/09/24 | 107 Storage | microwave stickers missing | B | Caretaker | 04/15/24 | Details |
04/09/24 | 107 | ceiling tiles missing/loose | A | Caretaker | 04/15/24 | Details |
04/09/24 | caretaker office/lunchroom | microwave stickers missing | B | Caretaker | 04/15/24 | Details |
06/24/24 | Male instructors office | ceiling tiles missing/loose | A | Principal | 07/02/24 | Details |